Crestron DIN-AP3 DIN Rail 3-Series Automation Processor
Operations & Installation Guide DOC. 7491A Automation Processor: DIN-AP3 25
DIN-AP3 Troubleshooting (Continued)
TROUBLE POSSIBLE
CAUSE(S)
CORRECTIVE
ACTION
Compilation
error
RLCMCVT166
and
RLCMCVT177.
Poor analog
versus serial
signal definition in
the SIMPL
Windows program.
Confirm properly
defined signal
definition in the
program.
System locks
up.
Various. Hold down SW-R
button on control
system front panel to
bypass program and
communicate directly
with processor. Refer
to “Troubleshooting
Communications” in
the Crestron 3-Series
Control System
Reference Guide
(Doc. 7150) at
www.crestron.com/
manuals
for more
details.
Cresnet device
does not
respond.
Device not wired
correctly.
Verify Cresnet wiring.
Improper NET ID
used.
Verify that device ID
matches NET ID in
the program.
Loss of
functionality due
to electrostatic
discharge.
Improper
grounding.
Check that all ground
connections have
been made properly.
(Continued on following page)