DIN Rail 3-Series Automation Processor Crestron DIN-AP3
10 • Automation Processor: DIN-AP3 Operations & Installation Guide – DOC. 7491A
Connectors, Controls & Indicators
# CONNECTORS*,
CONTROLS &
INDICATORS
DESCRIPTION
1 IO G, 8-1
(1) (1) 9-pin 3.5 mm
detachable terminal block
comprising (8) “Versiport”
digital input/output or analog
input ports (referenced to
GND);
Digital input: Rated for 0-24
volts dc, input impedance
20 kΩ, logic threshold
>3.125 V low/0 and <1.875 V
high/1;
Digital output: 250 mA sink
from maximum 24 volts dc,
catch diodes for use with “real
world” loads;
Analog input: Rated for
0
-
10 volts dc, protected to
24 volts dc maximum, input
impedance 21 kΩ with pull-up
resistor disabled;
Programmable 5 volts, 2 kΩ
2 PWR LED Amber indicates power
supplied to unit via either NET
port;
Green indicates firmware
upload is complete
3 NET LED Amber LED indicates Cresnet
bus activity
4 HW-R Button (1) Recessed miniature push
button for hardware reset
(reboots the processor)
(Continued on following page)