Wired Touchpanels Crestron Series 1600
Reserved Join Numbers
A reserved join number is a feature of the software that enables a designer to create a
button on a touchpanel page that either calls up the Setup Menu, ramps brightness,
etc. The table shown after this paragraph provides a list of reserved join numbers
available within the software.
Reserved Join Numbers for Series 1600 Touchpanels
JOIN NUMBER FUNCTION
V
ALUE
1016 Brightness Off
1017 Brightness Low
1018 Brightness Medium
1019 Brightness High
1023 Contrast Up
1024 Contrast Down
1035 Call up Setup Menu Not Applicable
1160 Keyclick Volume Up
1161 Keyclick Volume Down
1172 Keyclick On
1173 Keyclick Off
Problem Solving
Troubleshooting
The table below and on the next page provides corrective action for possible trouble
situations. If further assistance is required, please contact a Crestron customer
service representative.
Series 1600 Touchpanel Troubleshooting
TROUBLE
POSSIBLE
CAUSE(S)
CORRECTIVE ACTION
Touchpanel
does not
function.
Touchpanel is not
communicating to the
network.
Use Performance Viewport (via SIMPL
Windows or VT Pro-e) to poll the network.
Verify network connection to the touchpanel.
Verify touchpanel is in "CRESNET II" mode as
defined in the Interface Menu of the
"Configuring the Touchpanel".
Touchpanel is not
receiving network
power.
Confirm that power is supplied to the network.
Touchpanel is
incorrectly calibrated.
Enter SETUP MODE and recalibrate.
Touchpanel
is not
Incorrect network
wiring.
Touch screen to remove message and verify
correct wiring to all connectors.
responding
and screen
displays
"Network
Poll Error"
Touchpanel ID is not
set to match the NET
ID in the SIMPL
program.
Touch screen to remove message and enter
Performance Viewport (via SIMPL Windows or
VT Pro-e) to poll the network. Verify that the
NET ID for the touchpanel is properly set to
match the SIMPL program.
message. Touchpanel ID not
unique, two or more
units share same ID.
Enter Performance Viewport (via SIMPL
Windows or VT Pro-e) to poll the network.
Verify that each ID is used once.
16 Series 1600 Wired Touchpanels Operations & Installation Guide - DOC. 5836A