Crestron CP3 3-Series Control System™
Operations Guide DOC. 7316A 3-Series Control System™: CP3 7
Connectors, Controls & Indicators
# CONNECTORS*,
CONTROLS &
INDICATORS
DESCRIPTION
1
COMPUTER
(1) USB Type B female
USB 2.0 computer console port
(6 ft cable included).
For setup only.
2 PWR LED Green LED, indicates operating power
supplied from power pack or Cresnet
network
3 NET LED Amber LED, indicates communication with
the Cresnet system
4 MSG LED Red LED, indicates control system has
generated an error message
5 RESET BUTTONS
HW-R: Recessed pushbutton for hardware
reset
SW-R: Recessed pushbutton for software
reset
6 RELAY OUTPUT (1 – 8)
(2) 8-pin 3.5 mm detachable terminal block
comprising (8) normally open, isolated relays
Rated 1 Amp, 30 Volts AC/DC
MOV arc suppression across contacts
7 I/O
(1) 9-pin 3.5 mm detachable terminal block
comprising (8) “Versiportdigital input/output
or analog input ports (referenced to GND);
Digital Input: Rated for 0-24 Volts DC, input
impedance 20k ohms nominal, logic
threshold 1.24 Volts DC;
Digital Output: 250mA sink from maximum
24 Volts DC, catch diodes for use with “real
world” loads;
Analog Input: Rated for 0-10 Volts DC,
protected to 24 Volts DC maximum, input
impedance 21k ohms with pull-up resistor
disabled.
Programmable 5 Volts, 2k ohms pull-up
resistor per pin
8 IR SERIAL OUTPUT
(2) 8-pin 3.5 mm detachable terminal block
comprising (8) IR/Serial output ports
IR output up to 1.2 MHz
(Continued on following page)