Vue de la page 15
DIN Rail Cresnet
®
Distribution Block Crestron DIN-BLOCK
12
DIN Rail Cresnet
®
Block: DIN-BLOCK Operations & Installation Guide DOC. 6670B
DIN-BLOCK Data Signal LED Troubleshooting
Y Z DATA SIGNAL CONDITIONS
Bright Dim Both Y and Z data signals present
Off Bright Both data signals missing
Bright Bright Y data signal is present, Z is missing
Off Dim Z data signal is present, Y is missing
Dim Bright Y and Z data signals reversed
Check Network Wiring
Use the
Right Wire
In order to ensure optimum performance over the full range of the
installation topology, Crestron Certified Wire and only Crestron
Certified Wire may be used. Failure to do so may incur additional
charges if support is required to identify performance deficiencies
because of using improper wire.
Calculate
Power
CAUTION: Use only Crestron power supplies for Crestron equipment.
Failure to do so could cause equipment damage or void the Crestron
warranty.
CAUTION: Provide sufficient power to the system. Insufficient power
can lead to unpredictable results or damage to the equipment. Please use
the Crestron Power Calculator to help calculate how much power is
needed for the system (www.crestron.com/calculators
).
When calculating the length of wire for a particular Cresnet run, the wire
gauge and the Cresnet power usage of each network unit to be connected
must be taken into consideration. Use Crestron Certified Wire only. If
Cresnet units are to be daisy chained on the run, the Cresnet power
usage of each network unit to be daisy chained must be added together
to determine the Cresnet power usage of the entire chain. If the unit is
home-run from a Crestron system power supply network port, the
Cresnet power usage of that unit is the Cresnet power usage of the entire
run. The wire gauge and the Cresnet power usage of the run should be
used in the following equation to calculate the cable length value on the
equation’s left side.